Initial charge

Terminology of communication power supply
a set Lead storage battery After assembly, the first charge is called initial charge. The initial charge is the key work of the lead battery. Whether it is well done or not is directly related to the life and capacity This work should refer to the instructions of the battery factory. In addition, the first charge of a group of lead batteries that have been out of service for a period of time and have been stored in dry storage for several years before being reused is also called initial charge.
Chinese name
Initial charge
Foreign name
Initial Charge
Charging mode
Constant current charging
Discharge charging cycle
1、 Secondary

objective

Announce
edit
The purpose of initial charging is to put the lead oxide generated by long-term contact with air on the cathode plate electrolyte It reacts with sulfuric acid to become lead sulfate, and during the initial charging process, lead sulfate is reduced to fluffy lead. Because this kind of lead sulfate is more, it needs to be charged for a long time. [1]

condition

Announce
edit
① Requirements for AC power supply
During the initial charging period of the storage battery, ensure that the AC power supply is not interrupted within 75 hours. In particular, it is not allowed to stop charging within 24 hours after starting charging. Therefore, it is required to have at least two lines of mains power or one line of reliable mains power weak part oil turbine generator set. The voltage shall be within the range of 90-110% (342~418 V) of the rated value, and the phase connection shall be correct. The rectifier can work normally.
② Requirements for charging equipment
The over-voltage and over-current protection and fuse of the rectifier must be checked and adjusted. In case of failure, it shall be able to stop automatically and send alarm signals. The output of manual and automatic adjustment is normal, and the voltage and current stabilization shall meet the indicators specified by the manufacturer. The automatic current stabilizing part shall be used for load test for a certain time (not less than 2 hours) to ensure safety during charging. After the installation of all power equipment is completed, the initial charging can be carried out only after the wiring is correct, the insulation is good and the oil turbine generator set operates normally.
③ Requirements for concentrated sulfuric acid and distilled water and calculation of required quantity
The dilute sulfuric acid used for lead batteries must be pure, which is made by mixing pure sulfuric acid with distilled water (or pure water). The purity and impurity of the electrolyte have a great impact on the battery life. If it contains impurities, it is easy to generate natural discharge. The electrolyte contains more than 5% impurities, and it is possible to discharge the electricity within 24 hours. In particular, batteries that use the charging and discharging system are more harmful because they do not have supplementary charging. [2]

Final judgment

Announce
edit
According to the initial charging record, the cumulative amount of electricity charged into the battery should be 5~6 times of the rated capacity of the battery. The terminal voltage of each battery is above 2.7 "-- 2.75 V. At this time, the electrolyte bubbles rise, the positive plate is dark brown, and the negative plate is light gray. It can be clearly seen from the lead bridge that half is brown and half is gray. After the specific gravity is adjusted, the voltage will not rise for three hours, which indicates that the battery has been charged. [2]