Design description: none, building function: medical, drawing depth: construction drawing, Number of sheets: 1 sheet, Design content: air conditioning , clean
Description of the drawing of the purification air conditioner in the blood ward of the hospital: 1. No matter whether it is marked on the drawing or not, all the exhaust pipes in the operating room must be equipped with manual air volume regulating valves. 2. Unless otherwise noted, all air ducts separately connected to the clean air supply outlet are 320 * 160, and the air ducts separately connected to the clean upper air return outlet are 250 * 200. 3. The size of return air riser is 350 * 150 4. Unless otherwise specified, the size of all exhaust pipes is 200 * 160. 5. The lower return air inlet of the Class 100 ward is equipped with F6 medium efficiency filter screen, and other functional rooms are equipped with nylon screen. 6. The size of the lower air return outlet of the Class 100 ward is 795 * 345, including 700 * 289 * 97 medium efficiency filter screen; The lower air return outlet of clean corridor and auxiliary room is 395 * 345, including 325 * 289 * 97 medium efficiency filter screen. 7. AHU-1901~1905 air conditioning unit control panel is installed on the wall of the nurse station, 1.2m above the ground. See the plan for details.