This data is the cad construction drawing for the design of the 4-ton coal-fired boiler room. The boiler room has a capacity of one DZL2.8-0.7/95/70-A II type hot water boiler, with the boiler heating capacity of 2.8MW and the rated pressure of 0.7MPa. The boiler water supply temperature is 95 ℃, and the return water temperature is 70 ℃. ZR-6L automatic softener is selected as the water treatment equipment, with the water output of 5-7m3/h and the capacity of soft water tank of 5m3. The constant pressure mode of the hot water system is the constant pressure of the make-up pump. When the system pressure is lower than a certain value, the pump starts, and when the system pressure is higher than a certain value, the pump stops running; The pressure of the constant pressure point will be determined when the system is debugged. The foundation of circulating water pump and make-up water pump is designed as shock absorption foundation, with accurate design and detailed content, which can be downloaded for reference by netizens.

 4 ton coal-fired boiler room design cad construction drawing - Figure 1

4 ton coal-fired boiler room design cad construction drawing - Figure 1

Click to download the source file now