brand Xi'an Xichi | Valid until Long term effective |
Last update 2024-02-18 10:48 |
model CMC-470/3-LX |
Voltage 380V |
power 470KW |
Number of browses three hundred and sixty-eight |
470KW Xichi soft starter CMC-470/3-LX wholesale
470KW Xichi soft starter CMC-470/3-LX wholesale, Xi'an Xichi soft starter, CMC-LX soft starter, Chongqing soft starter manufacturer; CMC-250/3-LX bypass type soft starter, motor soft starter manufacturer, CMC soft starter wholesale 139-71230930, Xichi CMC-LX CMC-MX full series soft starter in stock, national warranty 18 months;
Xichi CMC-LX series soft starter 139-71230930 has multiple starting modes: current ramp starting, voltage ramp starting
Slope starting; Multiple parking modes: free parking and soft parking. Users can
Different starting and stopping modes shall be selected for specific use conditions.
1 Current ramp start
When using current ramp start mode
After the start command, its output current will follow the set curve
Increase until the output current reaches the set current limit
Im, The output current no longer increases, and the motor accelerates
After a period of time, the current starts to drop and the output voltage is rapid
Increase until full voltage output, and the starting process is completed.
2 Voltage ramp start
This starting mode is suitable for large inertia load, and
The starting can be greatly reduced in occasions with high dynamic stability requirements
Impact and mechanical stress.
3 sudden jump torque soft start
The sudden torque soft start is mainly applied to the load motor with large static resistance
Apply a large instantaneous starting torque to overcome the large static friction torque. Output in this mode
The voltage quickly reaches the set jump voltage. When the preset jump time is reached
Start smoothly according to the set starting voltage and ramp time until the start is completed.
4 Free parking
When the stop time (L008) is set to 0, it is free stop mode. When the soft starter is connected
After the stop command, the soft starter blocks the control relay of the bypass contactor and then blocks the main
The output of the circuit thyristor enables the motor to stop freely according to the load inertia.
. 5 Soft stop
When the parking time is not set to 0, the parking under full pressure is soft parking
When the machine stops under the mode, the soft starter first disconnects the bypass contactor, and the output voltage of the soft starter is
During the set soft stop time, it gradually decreases to the set soft stop termination voltage value, and the soft stop process
Turn the starter to free stop.