Cable model
YTTW(Y)-0.6/1kV
Executive standards
Product standard: rated voltage 0.6/1kV and below metal sheathed inorganic mineral insulated cables and terminals
Fire resistance test standard: BS 6387:2013 Performance Requirements for Cables to Maintain Line Integrity under Flame Conditions and BS 8491:2008 Assessment Method for Fire Integrity of Large Diameter Power Cables Used in Smoke and Heat Control Systems and Certain Other Fire Safety System Components Still in Progress
Scope of application
This product is suitable for communication In the lines with 50Hz and rated voltage not exceeding 0.6/1kV, they are mostly used in high-rise buildings, subways, stations, airports, power stations, shopping malls and other relatively closed or crowded important buildings and facilities.
Cable structure
conductor
Section Type 1 or type 2 copper conductor
insulation
High temperature resistant and incombustible inorganic mineral insulation material (mica tape /Ceramic silicone rubber belt), wrapped
Filling (selected according to cable specification)
Glass fiber rope
Metal sheath
Ordinary annealed copper or copper alloy, with good bending properties after special processing PE line
Outer sheath( YTTWY has this structure)
Low smoke and halogen-free plastic material is used, which has good flame retardant and protective effect
Specification range
1-core: 10~630mm two
2-core: 4~150mm two
3-core: 4~150mm two
4-core: 4~150mm two
5-core: 4~150mm two
3+1 core: 4~150mm two
3+2-core: 4~150mm two
4+1 core: 4~150mm two
Core identification
2-core: ● red ● blue
3-core: ● yellow ● green ● red
4-core: ● yellow ● green ● red ● blue
5-core: ● yellow ● green ● red ● blue ● yellow /Green
Or: ● yellow ● green ● red ● blue ● white
Sheath color
Orange (also according to customer requirements)
technical parameter
Rated voltage( U zero / U )
0.6/1kV
Maximum system voltage ( U m )
1.2kV
Temperature class
Maximum operating temperature of conductor: +90℃
Ambient temperature: -20℃~+45℃
Cable laying temperature: no less than 0 ℃ (when the ambient temperature is lower than 0 ℃, the cable shall be preheated)
Minimum bending radius during cable installation
D≤12 : 6D
12≤D≤20: 10D
20≤D≤40: 15D
D>40 :20D
Note: D is the outer diameter of the cable
Laying method
Pipe laying, tunnel laying, supporting overhead laying, hanging overhead laying, etc.