Except those used for heating asphalt in road constructionHeat conduction oil boilerIn addition, other heat transfer oil boilers shall generally have fixed boiler rooms.The design and construction location of these boiler rooms shall comprehensively consider safety, fire protection, environmental protection, economy and other factors, and shall meet the following requirements: 1. In principle, the boiler room of the conduction oil boiler should be built separately, and some small electric heating furnaces can be determined according to the situation; 2. The heat transfer oil boiler should not be directly located in the room with a large number of people (such as public bathrooms, classrooms, restaurants, shops, auditorium, waiting rooms, etc.) or above, below, adjacent to or on both sides of the main evacuation exit threeHeat conduction oil boilerIn addition to the unavoidable multi-storey building, the boiler room should be a single storey building, and should not be located in the basement or semi basement of the building; 4. The boiler room of the heat-conducting oil boiler shall not be connected with Class A, Class B and Class C fire hazard buildings using flammable liquids and rooms with flammable, explosive or other dangerous goods.If it is necessary to connect with other production plants, it should be separated by a whole firewall; 5. The fire separation between the boiler room of the heat-conducting oil boiler and the civil building shall not be less than 25 m, and the fire separation between the boiler room and the roadside of the roads outside the plant, and the roadside of the main (secondary) roads in the plant shall not be less than 15 m, 10 m (5 m) respectively;The fire lane in the plant shall be as short as possible, with a general width of not less than 3.5m and a clear height of not less than 4m; 6. The boiler room of the heat-conducting oil boiler shall be a building with Class I and Class II fire resistance rating; 7. The boiler room shall adopt light roof, otherwise the external wall or roof of the boiler room shall have a pressure relief area equal to at least 10% of the floor area of the boiler room (including the area of glass window, skylight, weak wall, etc.);The pressure relief place shall not be adjacent to the room and passageway with many people;
eightHeat conduction oil boilerThere shall be at least two exits in the boiler room of, which shall be respectively set on both sides and shall be kept unobstructed.The door from the boiler room to the outside shall be opened outwards, and shall not be locked or bolted during boiler operation.The doors of the operation room and production room shall be opened to the boiler room.Glass windows shall not be set on the wall adjacent to the living room and boiler room.