1、 Control mode
1、 One for use and one for standby: Control 1 # and 2 # water pumps. In automatic mode, it can work in "1 # main 2 # standby" or "2 # main 1 # standby". In two states, when the main pump fails, the standby pump will be put into operation automatically. In case of "manual" override, it can be controlled by the panel operating button. If the user requires to add the "dual-use" mode (that is, two pumps are used at the same time), please specify when ordering;
2、 Two for use and one for standby: Control 1 #, 2 # and 3 # water pumps, which can work in three states: "1 #, 2 # main and 3 # standby" or "2 #, 3 # main and 1 # standby" or "1 #, 3 # main and 2 # standby". When the main pump fails, the standby pump will be put into operation automatically. "Manual" start is controlled by operating buttons. If one main pump is turned off, it will become "one for use and one for standby". If the user requires to increase the "three for use" working mode (three pumps can be used at the same time), please specify when ordering;
3、 Three for use and one for standby: Control four water pumps 1 #, 2 #, 3 # and 4 #, which can work in four states: "1 #, 2 #, 3 # main 4 # standby" or "2 #, 3 #, 4 # main 1 # standby" or "1 #, 2 #, 4 # main 3 # standby" or "1 #, 3 #, 4 # main 2 # standby". When the main pump fails, the standby pump will automatically put into operation. When starting "manually", it is controlled by the panel operation button. If one main pump is turned off, it will become "two for use and one for standby". If two main pumps are turned off, it will become "one for use and one for standby". If the user requires to add the "four use" working mode (that is, four pumps are used at the same time), please order for details.