Guodian Nanzi PST693U transformer Protector
Main technical indicators
1 Scope of work
Current: 0.04In ~ 20In (In=high or In=1A);
Voltage: 1V~140V;
Frequency: 45Hz~55Hz.
2 Measurement accuracy
Current: 0.2 level (including harmonics);
Voltage, active power, reactive power and power factor: 0.5 level (including harmonics);
Frequency: ≤± 0.01Hz;
4-20mA output: 0.5 level.
3 Setting error
Setting value error: no more than ± 3%;
Action time error: definite time protection, not exceeding (± 1% setting value+40) ms; Inverse time protection, no more than 5% setting value or ± 40ms.
4 Remote signaling resolution
Less than 2ms.
5 GPS time synchronization
Minute pulse or second pulse: the interface provided by the GPS device is required to be an empty optocoupler, and the withstand voltage is greater than 50V;
IRIG-B: DC time code, RS485 interface.
6 Contact capacity
Tripping current and closing current of operation circuit: 0. high~high self adaption;
Tripping empty contact: high (DC220V closing capacity); Signal air contact: high (DC220V closing capacity).
7 Environmental conditions
Ambient temperature: - 25 ℃~+ 55 ℃;
Relative humidity: 5%~95% (no condensation and icing inside the product);
Atmospheric pressure: 66kPa~106kPa
8 Power consumption
AC current circuit: when In=high, each phase is not more than 0.5VA; When In=1A, each phase shall not be greater than 0.3VA.
AC voltage circuit: when rated voltage is applied, each phase shall not be greater than 0.5VA.
DC power supply Circuit: no more than 10W when working normally; When the device operates, it shall not be greater than 20W.
9 Overload capacity
AC current circuit: 2 times of rated current, continuous operation; 10 times rated current, 10s allowed; 40 times rated current, 1s allowed.
AC voltage circuit: 1.4 times rated voltage, continuous operation.
10 Insulation performance
10.1 Insulation resistance
Under normal test atmospheric conditions, the insulation resistance of the device between the external live circuit part and the exposed non live metal part and the shell, as well as between the electrically unconnected circuits, shall be measured with a 500V megger, and shall not be less than 100 M Ω.
10.2 Medium strength
Under normal test atmospheric conditions, the device can withstand a power frequency withstand voltage test with a frequency of 50Hz for 1min without breakdown, flashover and component damage. During the test, when voltage is applied to any of the tested circuits, the other circuits are equipotentially interconnected and grounded.
10.3 Impulse voltage
Under normal test atmospheric conditions, the device's DC input circuit, AC input circuit, output contact and other circuits to the ground, as well as between electrically unrelated circuits, can withstand 1.2/50 µ s standard lightning wave short-time impulse voltage test, and the open circuit test voltage is 5kV.
10.4 Damp heat resistance
The device can withstand the alternating damp heat test specified in Chapter 20 of GB/T 7261. The test temperature is+40 ℃± 2 ℃, the relative humidity is (93 ± 3)%, and the test time is 48h (the time of each cycle is 24h). Within 2h before the end of the test, measure the insulation resistance between the exposed non charged metal parts of each external live circuit part and the shell, as well as between the circuits that are not electrically connected, and the insulation resistance shall not be less than 1.5M Ω; The dielectric strength shall not be less than 75% of the specified dielectric strength test voltage.