I Product Introduction
HXGN □ - 12 series box type fixed AC metal enclosure switch The equipment (hereinafter referred to as ring main unit) is applicable to indoor AC high-voltage complete equipment with rated voltage of 3.6-12kV and rated frequency of 50Hz. Comply with the national standard GB3906-91 3-35kV Indoor AC Metal Enclosed Switchgear, KL404/T Indoor AC High voltage switch cabinet Technical Conditions for Ordering and IEC-420 AC Metal Enclosed Switchgear and Control Equipment of the Engineering Committee.
2、 Model meaning
H X G N port - 12
H: Ring network unit
10: Box structure
G: Fixed
N: Indoor use
Port: design serial number
12: Rated voltage KV
ZF: vacuum load switch
(R) : Fuse
Opening: features of operating mechanism
(S manual, D electric)
Port: rated current A
III Structure description
1. The frame of HXGN-10 ring main unit is assembled with foreign advanced technology profiles, and the overall structure is firm. The top of the cabinet is the bus room, the front of the bus room is the instrument room, and the middle and upper parts of the cabinet are the installation positions of the load beginning. The lower part is installed with current incoming and outgoing lines and other components (such as CT, PT). Each room is reliably separated.
2. The main switch adopts Italian advanced technology, and the imported ISARC load switch or FN12A-10D/630 pneumatic load switch with static contact insulation cover has stable and reliable performance. (The main switch can also use the vacuum load switch or sulfur hexafluoride switch according to user requirements)
3. The cabinet body has a perfect device to prevent electrical misoperation.
4. The cabinet body is small, occupies less land, and is safe and reliable.
4、 Technical data
S/N | project | Company | numerical value |
one | Rated voltage | KV | ten |
two | Rated voltage | Load switch cabinet | A | six hundred and thirty |
Combined electrical cabinet | one hundred and twenty-five |
three | Rated short-circuit making current (peak value) | KA | fifty |
four | Rated short-circuit breaking current | KA | thirty-one point five |
five | Rated active load breaking current | KA | six hundred and thirty |
six | 4s thermal stability current | KA | twenty |
seven | Rated dynamic stability current (peak value) | KA | fifty |
eight | 1min power frequency withstand voltage | KA | 42 (fracture, 48) |
nine | Lightning impulse withstand voltage | KA | 75 (fracture, 85) |
ten | Mechanical life | second | ten thousand |
eleven | Rated alternating current (composite apparatus) | A | three thousand one hundred and fifty |
twelve | Operation mode | | Manual or electric |
thirteen | Protection grade | | IP2X |
V Service conditions
Altitude: no more than 1000m.
Ambient air temperature: - 25 ℃ - 40 ℃
Relative humidity: the daily average value is not more than 95%, and the monthly average value is not more than 90%. There is no conductive dust, corrosive gas and water vapor, no fire and explosion hazards, and no frequent severe vibration.
6、 Ordering instructions:
The user must provide the following information when ordering:
1. Main wiring scheme number;
2. Secondary circuit wiring schematic diagram and terminal arrangement diagram. If there is no arrangement diagram for the terminal, it shall be in accordance with the manufacturer's regulations;
3. Model, specification and quantity of electrical components in the switch cabinet.