Fire dike Fire retardant coating Usage and price
Fire prevention of fire dike coating Price, quotation of fire retardant coating for petrochemical fire dike supplied by Yinuo Fire Protection Co., Ltd., and use of fire retardant coating for fire dike Used for storage of combustible materials in petrochemical enterprises and related units pot Fire protection of fire dike, spherical tank column, etc, Used to be used in: oil reserve depots, PetroChina, Sinopec, Sinochem, and local oil reserve departments door Etc.
Fire retardant coating for fire dike
It is made of inorganic and agricultural production system compound as the base material, with perlite Aluminum silicate Fiber, calcium carbonate, flame retardant, a kind of fire retardant coating made by mechanical mixing with water as the dispersion medium.
usage method
1 The fire dike shall be closed and able to withstand the static pressure of the oil contained and the destructive force caused by the earthquake to ensure its firmness and stability.
2 The fire dike shall be constructed of incombustible materials. The earth dike can be constructed of incombustible materials such as masonry and reinforced concrete when the soil source is difficult, but the inner side shall be earthed or coated with effective fire retardant coating. The top width of earth fire dike shall not be less than 0.5m.
3 The calculation * * * degree of vertical oil tank group fire dike shall ensure the effective volume demand in the dike. The actual * * * degree of the fire dike shall be 0.2m higher than the calculated * * * degree * * *. The actual * * * degree of the fire dike shall not be less than 1.0m, and shall not be * * * less than 2.2m (calculated from the pavement or terrace outside the fire dike). The degree of cofferdam of horizontal oil tank group shall not be less than 0.5m.
4 The pipeline crossing the fire dike shall be sealed with non combustible materials. It is strictly prohibited to open holes on the fire dike.
5 The site inside the fire dike may not be paved, but the site inside the tank group in collapsible loess, saline soil, expansive soil and other areas shall be provided with measures to prevent rainwater and spray water from soaking the tank foundation.